•  ZZYVP nitrogen packaging device is mainly used for constant nitrogen pressure control at the top of storage tank to protect materials from nitriding and safe nitrogen packaging device of storage tank consists of ZZDQ fast relief valve and ZZV micro-pressure regulating valve. The quick relief valve is composed of a pressure controller and a ZMQ-16K single-seat shutoff valve. When the pressure in the tank rises to the set pressure, the quick relief valve opens quickly and releases the excess pressure in the tank. When the pressure in the tank decreases, the micro-pressure regulating valve opens the valve and fills the tank with nitrogen. Because the micro-pressure regulating valve must be used under the pressure of 0.1 Mpa, and the field pressure is high, ZZYP type pressure regulating valve must be installed to reduce the pressure of the pressure regulating valve to less than 0.1 Mpa before it can be used. The nominal pressure is 0.1 Mpa, and the pressure can be set in stages from 0.5 Kpa to less than 66 Kpa. The temperature of the medium is less than 80 C.

     

    Characteristic

    1. The nitrogen supply (discharge) pressure of the nitrogen packaging device is easy to set and can be carried out under the condition of continuous production.

    2. The setting range of nitrogen pressure is wide, as low as 0.5 Kpa (50mm.w.c) and as high as Kpa, the ratio is 132 times. The effective area of pressure detection diaphragm is large, the setting spring stiffness is small, and the action is very sensitive.

    3. Adjustment:

    (1) Nitrogen supply pressure adjustment: select a set value such as 1Kpa (100mm. w. c) within the pressure regulation range of ZZV micro-pressure regulating valve, and change the pre-compression (stretching) amount of spring 3 by adjusting the adjustment screw 2;

    (2) Nitrogen release pressure adjustment: In the pressure controller part of ZZDQ quick release valve, the pre-compression of spring 4 is changed by adjusting seat 3. Generally, in order to avoid frequent opening and closing of nitrogen packages, the nitrogen release setting value should be far away from the nitrogen supply pressure value, such as 2Kpa (200mm. w. c).

    (3) Respiratory valve high setting value adjustment: After adjusting the above two setting values, in order to avoid frequent opening and closing of the breathing valve, the setting value of the breathing valve should be greater than the setting value of pressure relief.

     

    Parts materials

    零 件 名称
    材料
    阀体
    ZG230-450 ZG1Cr18 Ni9Ti
    阀杆、阀芯、阀座
    1Cr18 Ni9Ti
    膜片
    丁腈橡胶夹增强绦纶织物
    弹簧
    60Si2Mn
    波纹管
    1Cr18 Ni9Ti

     

    Main technical parametersIntroduction of Outer Size

    公称通径DN
    20
    25
    32
    40
    50
    65
    80
    100
    A
    192
    232
    308
    H
    629
    631
    652
    666
    689
    797
    837
    1050
    L
    150
    160
    180
    200
    230
    290
    310
    350
    G(Kg)
    18
    19
    21
    23
    25
    37
    50
    59
    法兰规格              单位:mm

     

    公称通径DN
    20
    25
    32
    40
    50
    65
    80
    100
    D
    105
    115
    140
    150
    165
    185
    200
    220
    D1
    75
    85
    100
    110
    125
    145
    160
    180
    B
    16
    18
    20
    22
    n-ф
    4-14
    4-18
    8-18
    f1×D2
    2×56
    3×65
    3×76
    3×84
    3×99
    3×118
    3×132
    3×156

Nitrogen sealing valve

ZZYVP nitrogen packaging device is mainly used for constant nitrogen pressure control at the top of storage tank to ...

扫描二维码分享到微信